Product Description
Transformer oil vacuum filter for power plant
Product model: ZYD-T
Body material: High carbon steel, stainless steel can be customized according to customer demand
working principle: Vacuum dehydration
Applicable products: Transformer oil
Product introduction
1. Purpose
Oil filter for UHV Transformer ( Transformer oil vacuum filter for power plant is especially used in 500kV, 750kV and 1000kV AC power grid, ± 660KV, ± 800kV DC power grid, this machine has strong vacuum degassing ability, oil-water separation ability, particle purification ability. It is commonly used for on-site maintenance of transformer and deep purification of high-grade new oil, imported oil, transformer oil, ultra-high voltage transformer oil, etc. It is also used for vacuum oiling and drying of transformer.
- Equipment parameters
project |
Parameter name |
Company |
ZYD-T-100 |
ZYD-T-150 |
ZYD-T-200 |
ZYD-T-300 |
ZYD-T-400 |
ZYD-T-500 |
Technical parameters of equipment |
flow |
L/H |
6000 |
9000 |
12000 |
18000 |
24000 |
30000 |
Ultimate vacuum |
Pa |
≤2 |
Working vacuum |
Pa |
≤30 |
working pressure |
Mpa |
≤0.5 |
Constant temperature control range |
ºC |
20-80 |
Power Supply |
V/HZ |
380V/50HZ(or according to the needs of users) |
Working noise |
dB(A) |
≤70 |
Total power |
kW |
60+6 |
90+10 |
120+10 |
180+15 |
240+15 |
270+35 |
Inlet and outlet pipe diameter |
mm |
40 |
50 |
50 |
65 |
65 |
80 |
Equipment weight |
kg |
1600 |
2400 |
2500 |
3800 |
4000 |
4500 |
Dimensions (L×W×H) |
Cm |
190x190x250 |
310x200x250 |
310x200x250 |
330x210x250 |
340×210x250 |
350×210×250 |
Oil treatment index |
Oil breakdown voltage |
KV |
≥75(GB/T507) |
Water content in oil |
PPm |
≤3(GB/T7600) |
Gas content in oil |
% |
≤0.1(GB/T423) |
Filtration accuracy |
μm |
≤1 |
acetylene |
% |
0 |
The overall dimensions and weight of the equipment are for reference only, subject to the actual objects.
3. Equipment features
Two stage vacuum large pumping speed and advanced dehydration and degassing system, adopting large area three-dimensional flash technology, can quickly and efficiently remove harmful components such as water, impurities and hydrocarbons in the oil, and improve the flash point and withstand voltage strength of insulating oil.
It can meet the requirements of vacuum pumping and vacuum oil injection for transformer body at installation or maintenance site.
Precision filtration system, high-quality filter element, multi-stage filtration and step-by-step encryption can effectively remove the mechanical impurities in the oil, and the filter element pollution degree automatic detection function is configured.
Automatic constant temperature control system, automatic liquid level control system, automatic defoaming control system, automatic pressure protection system and excellent configuration ensure high performance operation of the equipment.
Online oil filtering, unmanned operation, and operation status displayed by indicator light.
The machine is humanized design, low noise, easy to operate, long maintenance interval, low energy consumption, saving operation cost.
The whole machine is equipped with interlock safety protection, and the oil drainage system, vacuum system and heating system are interlocked.
It is equipped with filter element replacement indication and filter element saturation shutdown device.
There are electric leakage and overload shutdown devices to protect the motor.
It is equipped with phase sequence and missing phase protection function, and it can be used for safety control of sudden shutdown.
It is equipped with external vacuum pumping interface for transformer.
The oil in and out exchange function is provided.
4. Optional mode
According to the needs of users, PLC intelligent control, touch screen operation and dynamic display can be selected.
Select online moisture detector, online particle detector and flowmeter with accumulation function.
The frequency converter can be selected, and the flow can be selected according to the needs.
Structure of the whole machine: Mobile, fixed, trailer type (half axle or double axle), fully enclosed, covered, canvas shed, open type.
5.Customer site map
For the insulating oil with initial value of micro water content ≤ 50ppm and gas content ≤ 12% (volume ratio), after one-time treatment by the machine, it can reach the following requirements:
Micro water: ≤ 4ppm ± 2ppm
Gas: ≤ 0.1% (volume ratio)
Particle size: 5 μm or 1 μmthe pumping rate of this model: 1200-3000 m3 / h, it can vacuumize the large transformer above 220kV, realize vacuum oil injection, and can circulate hot oil to dry the transformer body.